Montluel Machine Coverage Matrix (Phase A — initial)
Date: 2026-07-16
Status: Phase A initial assessment. No Carrier source documents were provided for
this audit. Product-specific fields are therefore Unknown unless confirmed by repository
code. Per mission §13 rules, missing evidence is never converted into an assumption.
Status legend:
- Supported = a convergent end-to-end system test exists AND required components/correlations are present.
- Partial = architecture exists but physical model, configuration, or validation is incomplete.
- Not supported = required primitive/topology is absent.
- Unknown = source information insufficient to classify.
Source codes: [code] = repository evidence; [carrier] = authorized Carrier source (none used here); ? = Unknown.
Evidence base: docs/audits/heat_exchanger_architecture_audit.md (same date).
A. Archetypes under investigation
| ID | Archetype | Simulation status | Rationale (one line) |
|---|---|---|---|
| M1 | Air-cooled screw chiller (single circuit) | Partial | Components exist; FloodedEvaporator+Drum smoke-tested but not converged; air coil UA from geometry (FinCoil/MCHX) is geometry-capable. |
| M2 | Air-cooled screw chiller, dual-circuit / dual-module | Not supported | No shared-vessel primitive; cross-circuit edges rejected; example uses independent circuits only. |
| M3 | Water-cooled screw chiller / heat pump | Partial | Condenser/Evaporator/FloodedEvaporator exist; flooded model UA-only, no geometry, no dT_sat/dP analytic. |
| M4 | Flooded shell-and-tube evaporator/condenser machine | Partial | FloodedEvaporator/FloodedCondenser exist but UA-only, single-circuit, no shell-and-tube geometry; FloodedCondenser has an eqn-count defect. |
| M5 | BPHX evaporator/economizer machine | Partial | BphxEvaporator/Economizer exist with geometry+correlation; superheat/subcooling not enforced as residuals; DP not residual-coupled. |
| M6 | Scroll machine with BPHX or air-side coils | Partial | Compressors (Copeland/Danfoss) + BPHX/coils exist; no scroll-specific compressor model in core. |
| M7 | Reversible air-to-water heat pump | Partial | ReversingValve component exists; not wired into CLI factory; reversing logic + 4-way cycle not system-tested. |
| M8 | Centrifugal machine | Not supported | No centrifugal compressor component; no flooded centrifugal cycle test. |
| M9 | Dry-cooler / free-cooling | Partial | FreeCoolingExchanger exists (CLI arm run.rs:4092); no converged free-cooling system test verified. |
| M10 | Heat recovery / desuperheater | Not supported | No desuperheater component; no heat-recovery topology test. |
| M11 | One-, two-, three-pass water exchangers | Not supported (physically) | ShellAndTube{passes} ε-NTU is decorative (passes unused); pass count does not affect HTC/DP/UA. |
| M12 | One circuit running while another stopped (shared vessel) | Not supported | No shared-vessel primitive; staging example uses independent circuits. |
| M13 | Multiple compressors per circuit | Unknown | Topology allows multiple components per circuit, but no system test with ≥2 compressors on one circuit was verified. |
| M14 | Economizer / vapor injection | Partial | ScrewEconomizerCompressor + Economizer IHX exist; economized cycle has integration test (smoke, not converged-physics). |
| M15 | Confirmed current-product refrigerants | Unknown | CoolProp supports R134a/R410A/R454B/etc. in tests; which refrigerants ship in confirmed Montluel products is Unknown (no Carrier data). |
Note on "Partial": the codebase can draw the topology for several archetypes, but mission §13 requires separating "can draw the topology" from "can predict performance accurately." None reach Supported because no convergent end-to-end physics solve with geometry-based UA was verified in Phase A.
B. Detailed matrix (required columns)
Columns per mission §13. ? = Unknown (no evidence). Condensed where product-specific.
M1 — Air-cooled screw chiller (single circuit)
| Field | Value / Evidence |
|---|---|
| Product family | ? (no Carrier data) |
| Evidence/source | [code] components exist; no product doc |
| Cycle topology | single-circuit vapor-compression with economizer [code] |
| Compressor type | ScrewEconomizerCompressor [code] |
| Number of refrigerant circuits | 1 [code] |
| Number of modules | ? |
| Evaporator technology | FloodedEvaporator + Drum (per-circuit) [code] |
| Condenser technology | MchxCondenserCoil / FinCoilCondenser + fan bank [code] |
| Water/air path arrangement | air-cooled [code] |
| Pass count/options | N/A (air side) |
| Economizer | yes (IHX Economizer) [code] |
| Heat recovery | no |
| Refrigerant(s) | ? |
| Existing Entropyk components | screw econ compressor, flooded evap, drum, mchx/fin coil, fan, EXV |
| Missing components | converged-physics solve; geometry-based flooded UA |
| Missing topology capability | none (single circuit) |
| Missing correlations/data | flooded boiling correlation not in registry; air coil UA inline (not registry) |
| Zero-flow/staging support | single-circuit only |
| Validation dataset available? | No |
| Simulation status | Partial |
| Blocking issues | B2 (CoolProp build), B5 (red test) |
| Required implementation/test | converged air-cooled chiller system test |
M2 — Air-cooled screw chiller, dual-circuit / dual-module
| Field | Value / Evidence |
|---|---|
| Product family | ? |
| Evidence/source | [code] no shared-vessel primitive; multi_circuit.rs uses mocks |
| Cycle topology | two refrigerant circuits [code: rejected cross-circuit edges] |
| Compressor type | screw [code] |
| Number of refrigerant circuits | 2 (target) |
| Number of modules | 1 (shared vessel) or 2 (dual module) — both Not supported |
| Evaporator technology | needs shared-vessel flooded OR two modules |
| Condenser technology | air coil bank [code] |
| Water/air path arrangement | one common air stream (interlaced/face-split) — not modeled |
| Pass count/options | ? |
| Economizer | ? |
| Heat recovery | ? |
| Refrigerant(s) | ? |
| Existing Entropyk components | per-circuit flooded evap + drum only |
| Missing components | MultiCircuitFloodedEvaporator; shared-secondary wrapper; air-side multi-circuit topology |
| Missing topology capability | cross-circuit shared vessel (Phase D); air-side circuit interlace (Phase E) |
| Missing correlations/data | circuit-specific UA calibration |
| Zero-flow/staging support | Not supported (no primitive) |
| Validation dataset available? | No |
| Simulation status | Not supported |
| Blocking issues | Phase D + E prerequisites |
| Required implementation/test | shared-vessel dual-circuit converged test; one-circuit-off test |
M3 — Water-cooled screw chiller / heat pump
| Field | Value / Evidence |
|---|---|
| Product family | ? |
| Evidence/source | [code] condenser/evaporator/flooded exist |
| Cycle topology | vapor-compression, water-coupled [code] |
| Compressor type | screw [code] |
| Number of refrigerant circuits | 1 [code] |
| Number of modules | ? |
| Evaporator technology | DX Evaporator or FloodedEvaporator (UA-only) [code] |
| Condenser technology | Condenser (UA-only) / FloodedCondenser (defective eqn count) [code] |
| Water/air path arrangement | water-cooled, secondary as boundary or 4-port [code] |
| Pass count/options | decorative (passes unused) |
| Economizer | optional [code] |
| Heat recovery | no |
| Refrigerant(s) | ? |
| Existing Entropyk components | condenser, evaporator, flooded evap/cond, pump, brine boundary |
| Missing components | shell-and-tube geometry; water-side DP by pass; pass-aware effectiveness |
| Missing topology capability | fully-coupled live secondary ports (boundary mode is default) |
| Missing correlations/data | Gnielinski water-side; bundle boiling; tube-bundle condensation |
| Zero-flow/staging support | boundary regularization only |
| Validation dataset available? | No |
| Simulation status | Partial |
| Blocking issues | Phase B/C geometry + correlations |
| Required implementation/test | geometry-rated water chiller converged test |
M4 — Flooded shell-and-tube evaporator/condenser machine
| Field | Value / Evidence |
|---|---|
| Product family | ? (61XWHVZE referenced in mission — no data provided) |
| Evidence/source | [code] flooded evap/cond exist; mission §5.1 [carrier: not provided] |
| Cycle topology | flooded evap + flooded condenser [code] |
| Compressor type | ? |
| Number of refrigerant circuits | 1 [code]; 2 shared-vessel Not supported |
| Number of modules | ? |
| Evaporator technology | FloodedEvaporator (UA-only, single circuit, no geometry) [code] |
| Condenser technology | FloodedCondenser (UA-only, eqn-count defect) [code] |
| Water/air path arrangement | one common water circuit [carrier: mission §5.1, geometry not provided] |
| Pass count/options | standard 2-pass + 1/3 options [carrier: mission §5.1]; passes unused in code |
| Economizer | economizer BPHX [carrier: mission §5.1] |
| Heat recovery | ? |
| Refrigerant(s) | ? |
| Existing Entropyk components | flooded evap/cond (UA-only) |
| Missing components | ShellAndTubeGeometry; flooded boiling correlation; tube-bundle condensation; MultiCircuitFloodedEvaporator |
| Missing topology capability | shared-vessel two refrigerant circuits + intermediate tube sheet (Phase D) |
| Missing correlations/data | Cooper/Gorenflo pool boiling baseline; enhanced-tube correction; water-box losses; all product geometry Unknown |
| Zero-flow/staging support | not implemented |
| Validation dataset available? | No |
| Simulation status | Partial (single circuit) / Not supported (shared-vessel dual circuit) |
| Blocking issues | Carrier geometry data required for fixtures; Phases B/C/D |
| Required implementation/test | 1- and 2-circuit flooded chiller converged tests with geometry UA |
M5 — BPHX evaporator/economizer machine
| Field | Value / Evidence |
|---|---|
| Product family | ? |
| Evidence/source | [code] BPHX family + registry + geometry |
| Cycle topology | DX BPHX evap + BPHX economizer [code] |
| Compressor type | screw/scroll [code] |
| Number of refrigerant circuits | 1 [code]; dual-circuit BPHX Partial (Phase E) |
| Evaporator technology | BphxEvaporator (geometry+correlation) [code] |
| Condenser technology | BphxCondenser [code] |
| Water/air path arrangement | 4-port [code] |
| Pass count/options | N/A (plate) |
| Economizer | Economizer IHX [code] |
| Heat recovery | no |
| Refrigerant(s) | ? |
| Existing Entropyk components | full BPHX family + correlation registry |
| Missing components | superheat/subcooling as residual equations; DP residual coupling; dual-circuit BPHX |
| Missing topology capability | circuit-specific UA calibration (Phase E) |
| Missing correlations/data | SWEP BPHX data present (B5THx20, B8THx30); product-specific calibration Unknown |
| Zero-flow/staging support | correlation guards only |
| Validation dataset available? | No |
| Simulation status | Partial |
| Blocking issues | residual-coupled DP; Phase E dual-circuit |
| Required implementation/test | BPHX chiller converged test with residual DP |
M6 — Scroll machine (BPHX / air coils)
| Field | Value / Evidence |
|---|---|
| Product family | ? |
| Evidence/source | [code] vendor scroll data (Copeland/Danfoss) |
| Cycle topology | vapor-compression [code] |
| Compressor type | scroll (vendor data) [code]; no core scroll component model |
| Number of refrigerant circuits | 1 [code] |
| Evaporator/condenser technology | BPHX or air coil [code] |
| Pass count/options | N/A |
| Economizer | ? |
| Heat recovery | no |
| Refrigerant(s) | ? |
| Existing components | vendor compressor data, BPHX, coils |
| Missing components | scroll compressor component wired to vendor backend |
| Simulation status | Partial |
M7 — Reversible air-to-water heat pump
| Field | Value / Evidence |
|---|---|
| Evidence/source | [code] ReversingValve exists; not in CLI factory |
| Cycle topology | reversible [code] |
| Compressor type | ? |
| Circuits | 1 [code] |
| Evaporator/condenser | role-swap via reversing valve [code] |
| Reversing capability | component exists, not system-tested |
| Simulation status | Partial |
| Blocking issues | reversing valve CLI wiring; reversing system test |
M8 — Centrifugal machine
| Field | Value / Evidence |
|---|---|
| Evidence/source | [code] no centrifugal compressor component |
| Simulation status | Not supported |
| Blocking issues | centrifugal compressor model entirely absent |
M9 — Dry-cooler / free-cooling
| Field | Value / Evidence |
|---|---|
| Evidence/source | [code] FreeCoolingExchanger (CLI arm run.rs:4092) |
| Simulation status | Partial |
| Blocking issues | no converged free-cooling system test verified |
M10 — Heat recovery / desuperheater
| Field | Value / Evidence |
|---|---|
| Evidence/source | [code] no desuperheater component; no HR topology test |
| Simulation status | Not supported |
M11 — Water exchanger pass count (1/2/3 pass)
| Field | Value / Evidence |
|---|---|
| Evidence/source | [code] eps_ntu.rs:168-174 passes unused; lmtd.rs:53 F=0.9 hard-coded |
| Simulation status | Not supported (physically) — pass count does not affect UA/HTC/DP/effectiveness |
| Blocking issues | Phase B/C: real P-NTU multipass effectiveness + per-pass velocity/DP |
M12 — One circuit ON, other OFF (shared vessel)
| Field | Value / Evidence |
|---|---|
| Evidence/source | [code] no shared-vessel primitive |
| Simulation status | Not supported |
| Blocking issues | Phase D (zero-flow-safe multi-circuit) |
M13 — Multiple compressors per circuit
| Field | Value / Evidence |
|---|---|
| Evidence/source | topology allows multiple nodes per circuit [code]; no verified test |
| Simulation status | Unknown |
M14 — Economizer / vapor injection
| Field | Value / Evidence |
|---|---|
| Evidence/source | [code] ScrewEconomizerCompressor + Economizer IHX; integration test is smoke-only |
| Simulation status | Partial |
M15 — Confirmed current-product refrigerants
| Field | Value / Evidence |
|---|---|
| Evidence/source | CoolProp tests cover R134a/R410A/R454B [code]; which refrigerants ship in Montluel products |
| Simulation status | Unknown (no Carrier data) |
C. Coverage summary
| Status | Count | Archetypes |
|---|---|---|
| Supported | 0 | — |
| Partial | 9 | M1, M3, M4(single), M5, M6, M7, M9, M14 (+M4 single) |
| Not supported | 5 | M2, M8, M10, M11(physical), M12 |
| Unknown | 2 | M13, M15 |
Zero archetypes are Supported. The blockers are, in priority order:
- Shared-vessel multi-circuit primitive (Phase D) → unblocks M2, M4-dual, M12.
- Shell-and-tube geometry + correlations (Phases B/C) → unblocks M3, M4, M11.
- Residual-coupled DP + control semantics (Phase C) → unblocks M5.
- Carrier product geometry/validation data → required to move any archetype to Supported.
D. Data required from Carrier (to advance beyond Partial/Unknown)
The following are needed and must not be guessed (mission §1.4, §14):
- 61XWHVZE: shell ID, tube OD/ID, tube count per pass, active length per refrigerant circuit, tube enhancement type, water-box geometry, fouling factors, refrigerant(s), intermediate tube-sheet partition details, water-path layout through partitions.
- 30XF-Z: module/pass arrangement, one- vs two-pass evaporator options, pump/DP implications.
- BPHX dual-circuit: independent circuit UA calibration factors.
- Validation datasets (rated capacity/COP at AHRI/equivalent points) for each fixture.
Until provided, all product-specific fixture rows remain Unknown.