FloodedCondenser

Rust / SystemBuilder type: FloodedCondenser
Source: crates/components/src/heat_exchanger/flooded_condenser.rs


EN

Purpose & model

Flooded condenser on an inner HeatExchanger<EpsNtuModel> with optional subcooling control residual:

SC = (h_f(P)  h_out) / cp_l     # when subcooled
r_SC = SC  SC_target

Residuals & n_equations()

Base ≈ 3 (inner HX path); +1 with subcooling control (default target ~5 K).

Status: Prefer production Condenser + emergent_pressure for water-cooled machines. FloodedCondenser may lag the dual-mode / DoF discipline of FloodedEvaporator — treat as partial until fully aligned.

Ports

Refrigerant + secondary via inner exchanger / 4-port names when wired.

Calibration

Inner calib z_ua (default 1.0) when exposed.


FR

But

Condenseur noyé avec option de contrôle de sous-refroidissement.

Statut

Préférer Condenser + pression émergente en production. Fiche partielle tant que le DoF nest pas aligné sur FloodedEvaporator.

Calibration

Z_UA = 1 si exposé.