# FreeCoolingExchanger
Config types: `"FreeCoolingExchanger"`, `"FreeCooling"`
Source: free-cooling HX module
---
## EN
### Purpose & model
Free-cooling heat exchanger between two liquid loops (e.g. tower water ↔ chilled water) without vapor-compression. EffectivenessNTU or UA·LMTD between two single-phase streams.
```
Q = ε · C_min · (T_hot,in T_cold,in)
```
### Residuals
Two-stream energy balances + optional ΔP per leg.
### Ports
Hot and cold in/out (4-port).
### Calibration
`z_ua` default **1.0**.
### JSON
UA, fluids, optional secondary stream params — see CLI arm.
---
## FR
### But
Échangeur de **free-cooling** (liquideliquide), sans cycle frigo.
### Calibration